Direct Answer: Never force-reset a tripped factory VFD more than once. `OC` (Overcurrent) during zero-speed stop or motor-unplugged tests points directly to a shorted IGBT leg or failed optocoupler gate driver; `OV` points to braking resistor / grid swells; `GF` / `GFF` indicates a leaking hall transducer or damp motor cable.
Across Nepali crushers, extrusion lines, elevators, and garment boilers, a stopped Variable Frequency Drive brings production to an immediate halt. Worse yet, operators frequently press "RESET" five or ten times hoping a transient clears—blowing secondary gate resistors and charring multi-layer control PCBs that could otherwise be rebuilt cleanly in 24 hours.
Major VFD Brand Fault Code Lookup Matrix
| Fault Type | Delta / Inovance | Siemens V20/G120 | ABB ACS355/550 | Likely Root Cause |
|---|---|---|---|---|
| Overcurrent (OC) | `oc`, `ocA`, `ocd`, `ocn` | `F0001` / `F07801` | `2310` / `F0001` | Shorted IGBT, gate driver skew, or jammed mechanical shaft |
| Overvoltage (OV) | `ou`, `ov` | `F0002` | `3210` | Night grid swell (>270V+), decelerating high inertia without braking resistor |
| Ground Fault (GF) | `GFF` | `F0021` / `A07850` | `2330` | Moisture in motor terminal box OR faulty internal CT / Hall transducer |
| Undervoltage / Dead | `Lv` / Blank Keypad | `F0003` | `3220` | Burned pre-charge resistor, dried Nichicon DC bus cap, dead SMPS IC |
3 Safe Pre-Shipping Checks Before Calling or Mailing a Drive
- Wait 10 minutes after power-off so the 600V–750V DC bus capacitors discharge fully below 24V before touching terminals.
- Unplug U/V/W motor cables and test winding-to-earth insulation on the motor with a 500V megger.
- Do not reconnect mains if an `OC` or `GFF` persists un-loaded—send nameplate & fault photos to our VFD Drive Repair Lab or compare costs on VFD Repair vs Replace.