VFD Fault Codes Explained (OC, OV, GF): Troubleshooting Motor Drives in Nepal

By Er. Krishna Shah November 21, 2026 8 min read
Direct Answer: Never force-reset a tripped factory VFD more than once. `OC` (Overcurrent) during zero-speed stop or motor-unplugged tests points directly to a shorted IGBT leg or failed optocoupler gate driver; `OV` points to braking resistor / grid swells; `GF` / `GFF` indicates a leaking hall transducer or damp motor cable.

Across Nepali crushers, extrusion lines, elevators, and garment boilers, a stopped Variable Frequency Drive brings production to an immediate halt. Worse yet, operators frequently press "RESET" five or ten times hoping a transient clears—blowing secondary gate resistors and charring multi-layer control PCBs that could otherwise be rebuilt cleanly in 24 hours.

Major VFD Brand Fault Code Lookup Matrix

Fault Type Delta / Inovance Siemens V20/G120 ABB ACS355/550 Likely Root Cause
Overcurrent (OC)`oc`, `ocA`, `ocd`, `ocn``F0001` / `F07801``2310` / `F0001`Shorted IGBT, gate driver skew, or jammed mechanical shaft
Overvoltage (OV)`ou`, `ov``F0002``3210`Night grid swell (>270V+), decelerating high inertia without braking resistor
Ground Fault (GF)`GFF``F0021` / `A07850``2330`Moisture in motor terminal box OR faulty internal CT / Hall transducer
Undervoltage / Dead`Lv` / Blank Keypad`F0003``3220`Burned pre-charge resistor, dried Nichicon DC bus cap, dead SMPS IC

3 Safe Pre-Shipping Checks Before Calling or Mailing a Drive

  1. Wait 10 minutes after power-off so the 600V–750V DC bus capacitors discharge fully below 24V before touching terminals.
  2. Unplug U/V/W motor cables and test winding-to-earth insulation on the motor with a 500V megger.
  3. Do not reconnect mains if an `OC` or `GFF` persists un-loaded—send nameplate & fault photos to our VFD Drive Repair Lab or compare costs on VFD Repair vs Replace.